206
16.1.4 Device address
Bit/Word
Type
Address
Format
Range
Notes
B
I1
dddbb
ddd: 000~254 bb: 00~15
See Note on AB I/O addressing after section 14.2.
B
O0
dddbb
ddd: 000~254 bb: 00~15
See Note on ABI/O addressing after section 14.2.
B
B3, 10~13
dddbb
ddd: 000~254 bb: 00~15
File number is fixed, specify both Element and Bit
B
Bfn*
fffdddbb fff: 7, 10~254 ddd: 000~254
bb:00~15
File, Element and bit must be specified
B
NfnBit*
fffdddbb fff: 7, 10~254 ddd: 000~254
bb:00~15
Both File and Element must be specified
W
N7, 10~15
ddd
ddd: 000~254
File number is fixed, specify Element
W
Nfn*
fffddd
fff: 7, 10~254 ddd: 000~254
Both File and Element must be specified
W
F8 (N8)
ddd
ddd: 000~255
Floating Point words
W
Ffn*
fffddd
fff: 7, 10~254 ddd: 000~254
Both File and Element must be specified
W
T4 SV,PV
ddd
ddd: 000~254
PV is timer accumulator, SV is preset
W
C5 SV,PV
ddd
ddd: 000~254
PV is counter accumulator, SV is preset
Note:
Attempting to access a device that is not defined in PLC memory causes the
HMI to display the “PLC no response” error message.
Note:
The PLC’s memory range may vary within the range supported by the driver. Use appropriate addresses.
Note:
*
The NfnBit, Bfn, Nfn and Ffn device types allow access to any data file (fff) and element (nnn) in memory. fff specifies
the data file 000-254, and nnn specifies the element number 000-254. For example, to specify Integer data file 15, element 7
(N15:7), select Nfn as the device type and enter 015007 as the Device address.
See Note 16.3.5 for more information on formatting Device Addresses.