Appendix B. Status, Settings, and Data Table Information (Status/Settings/DTI)
Battery
(p. 473).
Low12VCount
Station Status:
Number of times voltage has
dropped below 12V
Keyboard:
Status Table
≈ line 21
CRBasic:
variable = status.keyword
Increments by 1 each time the primary CR1000
supply voltage drops below ≈9.0. Updated with e
ach
Status
table update. The following applies to the
CR800 and CR1000 dataloggers. A variation may
apply to the C6 and CR3000: The 12 Vdc-low
comparator triggers at about 9.0 Vdc. The
minimum-specified input voltage of 9.6 Vdc will not
cause a 12 Vdc low condition, but a 12 Vdc low
condition will stop program execution before
measurements are compromised.
reset only
LONG
count
0
0 to 99
0 = reset
Low5VCount
Station Status:
Number of times voltage has
dropped below 5V
Keyboard:
Status Table
≈ line 22
CRBasic:
variable = status.keyword
Number of occurrences of the 5 Vdc supply dropping
below a functional threshold.
reset only
LONG
count
0
0 to 99
0 = reset
Table 177.
Status/Settings/DTI: M
Keyword
Alias,
Access,
Description
Read/Write,
DataType,
Units
Default
Value
Normal
Range
MaxBuffDepth
Keyboard:
Status Table
≈ line 43
CRBasic:
variable = status.keyword
Maximum number of buffers the CR1000 will use to
process lagged measurements.
read/write
LONG
no units
0
?
MaxPacketSize
Settings Editor:
Max Packet Size
Keyboard:
Settings (General)
≈ line 8
CRBasic:
variable = settings.keyword
;
SetSettings()
Maximum number of bytes per data collection
packet.
read/write
LONG
bytes
1000
?
MaxProcTime
Keyboard:
Status Table
≈ line 41
CRBasic:
variable = status.keyword
Maximum time required to run through processing
for the current scan. Value is reset when the scan
exits. Calculated on-the-fly. See
MeasureTime
(p.
ProcessTime
(p. 625),
SkippedScan
(p. 628),
MaxProcTime
(p. 620).
read/write
LONG
μs
n/a
0
= reset
MaxSlowProcTime()
Keyboard:
Status Table
≈ line 49
CRBasic:
variable = status.keyword
Maximum time required to process a
SlowSequence
scan in the CRBasic program.
0
until a scan runs.
See
LastSlowScan
(p. 619),
SkippedSlowScan
(p. 628),
SlowProcTime
(p. 629).
read/write
LONG array
μs
0
until scan
0 = rest
620
Summary of Contents for CR1000
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 40: ......
Page 60: ...Section 4 System Quickstart Figure 16 PC200W View Line Graph 60 ...
Page 96: ......
Page 98: ...98 ...
Page 302: ......
Page 453: ...Section 8 Operation Figure 115 Using the Keyboard Display 453 ...
Page 456: ...Section 8 Operation Figure 118 Real Time Custom 456 ...
Page 457: ...Section 8 Operation 8 8 1 3 Final Memory Tables Figure 119 Final Memory Tables 457 ...
Page 458: ...Section 8 Operation 8 8 2 Run Stop Program Figure 120 Run Stop Program 458 ...
Page 460: ...Section 8 Operation Figure 122 File Edit 460 ...
Page 461: ...Section 8 Operation 8 8 4 PCCard Memory Card Display Figure 123 PCCard CF Card Display 461 ...
Page 478: ......
Page 506: ......
Page 536: ......
Page 636: ......
Page 642: ......
Page 644: ......
Page 676: ......
Page 677: ......