Appendix B. Status, Settings, and Data Table Information (Status/Settings/DTI)
pppDialResponse
Settings Editor:
PPP Dial Response
Keyboard:
Settings (TCP/IP)
≈ line 29
CRBasic:
variable = settings.keyword
;
SetSettings()
Specifies the response expected after dialing a
modem before a PPP connection can be established.
CRBasic program will recompile if changed from
NULL to not NULL, or from not NULL to NULL.
read/write
STRING
CONNECT
n/a
pppInterface
Settings Editor:
PPP Interface
Keyboard:
Settings (TCP/IP)
≈ line 23
CRBasic:
variable = settings.keyword
;
SetSettings()
Controls which CR1000 communication port PPP
service is configured for. Warning: if this value is
set to
CS I/O ME
, do not attach any other devices to
the
CS I/O
port. A change will cause the CRBasic
program to recompile.
read/write
LONG
0 (inactive)
???
pppIPAddr
Keyboard:
Settings (TCP/IP)
≈ line 24
Settings Editor:
PPP IP Address
CRBasic:
variable = settings.keyword
;
SetSettings()
Specifies the IP address that is used for the PPP
interface if that interface is active (the
PPP Port
/
PPP Interface
setting needs to be set to something
other than
Inactive
). Syntax is
nnn.nnn.nnn.nnn
.
A value of
0.0.0.0
or an empty string will indicate
that DHCP must be used to resolve this address as
well as the subnet mask.
read/write
STRING
0.0.0.0
0–255.0–
255.0–255.0–
255
pppIPMask
Settings Editor: ???
Keyboard:
Status Table
≈ line 25
CRBasic:
variable = settings.keyword
;
SetSettings()
read/write
STRING
none
0–255.0–
255.0–255.0–
255
pppPassword
Settings Editor:
PPP tab: Password
Keyboard:
Status Table
≈ line 27
CRBasic:
variable = settings.keyword
;
SetSettings()
Specifies the password that is used to log in to the
PPP server when the PPP interface setting is set to
one of the client selections. Also specifies the
password that must be provided by the PPP client
when the PPP interface setting is set to one of the
server selections.
read/write
STRING
none
0 to 63
characters
pppUsername
Settings Editor:
PPP User Name
Keyboard:
Settings (TCP/IP)
≈ line 26
CRBasic:
variable = settings.keyword
;
SetSettings()
Specifies the user name that is used to log in to the
PPP server.
read/write
STRING
none
0 to 63
characters
ProcessTime
Keyboard:
Status Table
≈ line 40
CRBasic:
variable = status.keyword
Processing time of the last scan. Time is measured
from the end of the
EndScan
instruction (after the
measurement event is set) to the beginning of the
EndScan
(before the wait for the measurement event
begins) for the subsequent scan. Calculated on-the-
fly. See
MeasureTime
(p. 621),
MaxProcTime
(p.
read only
LONG
μs
0
n/a
625
Summary of Contents for CR1000
Page 2: ......
Page 4: ......
Page 6: ......
Page 32: ......
Page 36: ......
Page 38: ......
Page 40: ......
Page 60: ...Section 4 System Quickstart Figure 16 PC200W View Line Graph 60 ...
Page 96: ......
Page 98: ...98 ...
Page 302: ......
Page 453: ...Section 8 Operation Figure 115 Using the Keyboard Display 453 ...
Page 456: ...Section 8 Operation Figure 118 Real Time Custom 456 ...
Page 457: ...Section 8 Operation 8 8 1 3 Final Memory Tables Figure 119 Final Memory Tables 457 ...
Page 458: ...Section 8 Operation 8 8 2 Run Stop Program Figure 120 Run Stop Program 458 ...
Page 460: ...Section 8 Operation Figure 122 File Edit 460 ...
Page 461: ...Section 8 Operation 8 8 4 PCCard Memory Card Display Figure 123 PCCard CF Card Display 461 ...
Page 478: ......
Page 506: ......
Page 536: ......
Page 636: ......
Page 642: ......
Page 644: ......
Page 676: ......
Page 677: ......