3. Program Error
I - 72
Error No.
Details
Remedy
P243 VARIABLE
ERR.
An invalid variable has been specified in
the left or right side of an operation
expression.
• Correct the program.
P252 PAT.&COOD-ROT
A coordinate rotation related command
(G68, G69) was issued during figure
rotation.
• Reconsider the program.
P260
NO COOD-RT SPC
Even though there were no coordinate
rotation specifications, a coordinate
rotation command was issued.
• Check the specifications.
P270
NO MACRO SPEC
A macro specification was commanded
though there are no such command
specifications.
• Check the specifications.
P271
NO MACRO INT.
A macro interrupt command has been
issued though it is not included in the
specifications.
• Check the specifications.
P272 MACRO
ILL.
A statement and a macro statement exist
together in the same block.
• Reconsider the program and place the
executable statement and macro statement
in separate blocks.
P273
MACRO OVERCALL
The number of macro call nests
exceeded the specifications.
• Reconsider the program and correct it so that
the macro calls do not exceed the limit
imposed by the specification.
P275
MACRO ARG. EX.
The number of macro call argument type
II sets has exceeded the limit.
• Reconsider the program.
P276 CALL
CANCEL
A G67 command was issued though it
was not during the G66 command modal.
• Reconsider the program.
• The G67 command is the call cancel
command and so the G66 command must be
designated first before it is issued.
P277
MACRO ALM MESG
An alarm command has been issued in
#3000.
• Refer to the operator messages on the DIAG
screen.
• Refer to the instruction manual issued by the
machine manufacturer.
P280
EXC. [ ‚
The number of parentheses "[" or "]"
which can be commanded in a single
block has exceeded five.
• Reconsider the program and correct it so the
number of "[" or "]" does not exceed five.
P281
[ ‚ ] ILLEGAL
The number of "[" and "]" parentheses
commanded in a single block does not
match.
• Reconsider the program and correct it so that
"[" and "]" parentheses are paired up
properly.
P282 CALC.
IMPOSS.
The arithmetic formula is incorrect.
• Reconsider the program and correct the
formula.