3.47
EDH0162En1040 – 06/99
MM4005
EO — Automatical execution on power on
Usage
IMM
PGM
MIP
Syntax
xxEOnn
or
EO?
Parameters
Description
xx
[int]
— Program number to execute on power on.
nn
[int]
— Number of times on execution.
?
— Read program number to execute and number of times
of execution.
Range
xx
—
1
to
127.
nn
—
1
to
2147385345
.
Units
xx
— None.
nn
— None.
Defaults
xx
Missing: 0 (no program execution on power on).
Out of range: Error F.
Floating point: Error A.
nn
Missing: 1 (one time of execution).
Out of range: Error C.
Description
This command sets the program number that is automatically executed on
power on. If
xx
is zero or missing, no program is executed. If
nn
is missing,
the
xx
numbered program is executed one time.
Returns
If the sign
“?”
takes place of the
nn
value and
xx
missing, this command
reportes the number of the program that is executed on power on and
number of times of execution.
Errors
A
—
Unknown message code.
C
—
Parameter out of limits.
F
—
Program number incorrect.
Rel. Commands
EX
—
Execute a program.
Example
2EO
|
Set program #2 to be executed one time on power on.
EO?
|
Read executed on power on program number.
EO, 2, 1
|
Controller tells the program #2 to be executed one time on power
on.
EO
|
Reset automatical execution - no program is executed on power on.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com