3.99
EDH0162En1040 – 06/99
MM4005
PW — Save parameters
Usage
IMM
PGM
MIP
Syntax
xxPW
Parameters
Description
xx
[int]
— Axis number.
Range
xx
—
0
to
4.
Units
xx
— None.
Defaults
xx
Missing: 0.
Out of range: Error B.
Floating point: Error A.
Description
This command saves in non-volatile memory all parameters of the selected
xx
axis that have been changed through on-line commands or from within a
program. If the axis specifier
xx
is not present or set to 0, parameters of all
axes will be saved.
For a list and description of the axis parameters that are stored in non-
volatile memory see the System Setup paragraph of the Introduction sec-
tion.
NOTE
Since this command is equivalent to making changes in SETUP mode, it
is valid only when motor power is turned off. If the command is issued
when the motor power is on, the controller will ignore it and report
error D.
NOTE
Before saving, make sure that the new set of parameters is correct and
safe to use. Also, it is good practice to verify that the parameter saving
procedure worked properly by issuing the TB or TE command after-
wards.
Returns
None.
Errors
A
—
Unknown message code.
B
—
Incorrect axis number.
D
—
Unauthorized execution.
U
—
Failure while accessing the EEPROM.
Rel. Commands
All device, motion and filter parameter setting commands.
Example
2KD0.02, 2UF |
Set Kd parameter of axis #2 to 0.02 and update filter.
… |
… |
Verify the new parameter is working fine.
… |
2PW
|
Save parameters of axis #2 to non-volatile memory.
TE |
Read error register.
TE@
|
Controller returns a no error code.