3.19
EDH0162En1040 – 06/99
MM4005
AM — Set analog input mode
Usage
IMM
PGM
MIP
Syntax
xxAMnn
or
[xx]AM?
Parameters
Description
xx
[int]
— Analog input port number.
nn
[int]]
— Analog input mode.
Range
xx
—
0
to
4.
nn
—
0
to
3
.
Units
xx
— None.
nn
— None.
Defaults
xx
Missing: 0.
Out of range: Error E.
Floating point: Error E.
nn
Missing: 0.
Out of range: Error C.
Description
The MM4005 controller possess four analog inputs that user can program
each input tension level with the AM command.
• If
nn
= 0 or missing:
±10 V tension input range.
• If
nn
= 1:
±5 V tension input range.
• If
nn
= 2:
0 to 10 V tension input range.
• If
nn
= 3:
0 to 5 V tension input range.
Returns
If the
“?”
sign takes place of
nn
parameter and
xx
is missing, the controller
returns the actual analog input mode.
Errors
C
—
Parameters out of limits.
E
—
Incorrect I/O channel number.
Rel. Commands
YR
—
Read a value from an user analog port and affect variable.
YO
—
Send a value to an user analog port.
Example 1AM2
|
Set 0 to 10 V analog range at the input port #1.
1AM?
|
Request the actual analog input port #1 mode.
1AM2
|
Controller returns the actual analog input port #1 mode.
AM
|
Initializes all analog input ports to default mode (±10 V).
AM?
|
Request all actual analog input modes.
AM, 1AM0, 2AM0, 3AM0, 4AM0
|
Controller returns all actual analog input modes.