3.91
EDH0162En1040 – 06/99
MM4005
OR — Search for home
Usage
IMM
PGM
MIP
Syntax
xxORnn
Parameters
Description
xx
[int]
— Axis number.
nn
[int]
— Home search position option.
Range
xx
—
0
to
4.
nn
—
0
to
2.
nn = 0
: Move to zero position instead of origin search.
nn = 1
: Search mechanical zero and encoders top zero.
nn = 2
: Search mechanical zero, but do not search
encoders top zero.
Units
xx
— None.
nn
— None.
Defaults
xx
Missing: 0.
Out of range: Error B.
Floating point: Error A.
nn
Missing: 1.
Out of range: Error C.
Description
This command executes a home search routine on the axis specified by
xx
.
If
xx
is missing or set to 0, a home search is initiated sequentially on all
installed axes, in the order specified in the General SETUP utility on the
front panel.
For details on how to set the home search axes sequence see the System
Setup paragraph of the Introduction section.
For a detailed description of the home search routine see the Home Search
Motion Profile Section in the Motion Control Tutorial section.
NOTE
There is a maximum allowed time for this command to execute, defined
in the front panel General SETUP menu. If the motion device does not
find the home position in the specified time, the controller stops the
search and turns motor power off.
NOTE
This command should be executed once every time the power is turned
on or the controller is reset by using the RS command. There is no need
to issue this command in any other case since the controller always
keeps track of position, even when the motor power is off.
Returns
None.
Errors
A
—
Unknown message code.
B
—
Incorrect axis number.
C
—
Paramètre hors limites.
Rel. Commands
DH
—
Define home.
OH
—
Set home search high velocity.
SH
—
Set home preset position.
Example
3OR1
|
Perform a search of mechanical zero and encoders top zero, on axis
#3.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com