20138
[Channel %1: ] Block %2 motion synchronous action %3 command axis %4 cannot be traversed
Parameters:
%1 = Channel number
%2 = Block number, line number
%3 = Synact ID
%4 = Axis name
Explanation:
The axis that should be traversed out of a synchronized action is not available
The following causes are possible:
- The axis is being or will be traversed by the NC program.
This motion can also be made indirectly by means of continuous-path mode or an active frame.
- A superimposed motion is active for the axis.
- The axis is active as a following axis of a coupling.
- An interpolatory compensation, such as temperature compensation, is active for the axis.
Reaction:
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Modify part program.
Programm
continuation:
Clear alarm with the RESET key. Restart part program
20139
[Channel %1: ] Block %2 motion synchronous action: %3 invalid marker
Parameters:
%1 = Channel number
%2 = Block number, line number
%3 = Synact ID
Explanation:
Setting or deleting of a marker in the motion-synchronous action is not possible.
Possible causes:
SETM(): Maximum number of markers exceeded; marker has already been set.
CLEARM(): Specified marker is not within permissible value range.
Reaction:
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
SETM(): use marker in valid value range; do not set the marker again.
CLEARM(): use marker in valid value range.
Programm
continuation:
Clear alarm with the RESET key. Restart part program
20140
[Channel %1: ] Traversing of command axis %2 see NC alarm %3 parameter %4
Parameters:
%1 = Channel number
%2 = Axis
%3 = NC alarm
%4 = Additional parameter
Explanation:
An NC alarm was detected for a command axis which is to be traversed from a synchronized action. The NC alarm is
indicated by an MMC alarm number in the 3rd parameter. If there is any additional information, this will be provided in a
4th parameter.
Reaction:
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
See help information for the additional alarms.