Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
L
573
8400 StateLine C | Reference manual
Parameter reference
Parameter list | C00247
C00247
C00249
C00265
C00270
C00271
C00272
C00273
Parameter | Name:
C00247 | L_PCTRL_1: Window setpoint reached
Data type: INTEGER_16
Index: 24328
d
= 5F08
h
From version 06.00.00
FB
L_PCTRL_1
: Window for comparison operation "actual value = setpoint"
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
%
100.00
2.00 %
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00249 | L_PT1_1: Time constant
Data type: UNSIGNED_16
Index: 24326
d
= 5F06
h
FB
L_PT1_1
: Time constant Tn
Setting range
(min. value | unit | max. value)
Lenze setting
0
ms
5000
2000 ms
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00265 | SLVC: Tn torque controller
Data type: UNSIGNED_8
Index: 24310
d
= 5EF6
h
This code is for device-internal use only and must not be written to by the user!
Parameter | Name:
C00270 | SC: Freq. current setpoint filter
Data type: UNSIGNED_16
Index: 24305
d
= 5EF1
h
Frequency to be inhibited by the current setpoint filter at sensorless control for synchronous motors (
SLPSM
).
Setting range
(min. value | unit | max. value)
Lenze setting
40.0
Hz
1000.0
200.0 Hz
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
;
MOT
Scaling factor: 10
Parameter | Name:
C00271 | SC: Width of current setpoint filter
Data type: UNSIGNED_16
Index: 24304
d
= 5EF0
h
Frequency width of the current setpoint filter at sensorless control for synchronous motors (
SLPSM
)
• Width around the frequency to be inhibited (
C00270
).
Setting range
(min. value | unit | max. value)
Lenze setting
0.0
Hz
500.0
0.0 Hz
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
;
MOT
Scaling factor: 10
Parameter | Name:
C00272 | SC: Depth of current setpoint filter
Data type: UNSIGNED_16
Index: 24303
d
= 5EEF
h
Damping of the current setpoint filter at sensorless control for synchronous motors (
SLPSM
)
Setting range
(min. value | unit | max. value)
Lenze setting
0
dB
100
0 db
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
;
MOT
Scaling factor: 1
Parameter | Name:
C00273 | Moment of inertia
Data type: UNSIGNED_32
Index: 24302
d
= 5EEE
h
From version 03.00.00
Moment of inertia for setpoint feedforward control at sensorless vector control (
SLVC
)
Setting range
(min. value | unit | max. value)
Lenze setting
0.00
kg cm^2
600000.00
0.00 kg cm^2
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
;
MOT
Scaling factor: 100
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com