Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
L
325
8400 StateLine C | Reference manual
Technology applications
TA "Switch-off positioning"
Outputs
GP: GeneralPurpose
The following inputs are interconnected with logic/arithmetic functions on application level for free usage.
"GeneralPurpose" functions
nGPAnalogSwitchIn1_a
nGPAnalogSwitchIn2_a
INT
Analog switch
: Input signals
• The input signal selected via the selection input
bGPAnalogSwitchSet
is output at
output
nGPAnalogSwitchOut_a
.
bGPAnalogSwitchSet
BOOL
Analog switch
: Selection input
FALSE
nGPAnalogSwitchOut_a
=
nGPAnalogSwitchIn1_a
TRUE
nGPAnalogSwitchOut_a
=
nGPAnalogSwitchIn2_a
nGPArithmetikIn1_a
nGPArithmetikIn2_a
INT
Arithmetic
: Input signals
• The arithmetic function is selected in
C00338
.
• The result is output at output
nGPArithmetikOut_a
.
nGPMulDivIn_a
INT
Multiplication/Division
: Input signal
• The factor for the multiplication can be set in
C00699/1
(numerator) and
C00699/2
(denominator).
• The result is output at output
nGPMulDivOut_a
.
bGPDigitalDelayIn
BOOL
Binary delay element
: Input signal
• The on-delay can be set in
C00720/1
.
• The off-delay can be set in
C00720/2
.
• The time-delayed input signal is output at output
bGPDigitalDelayOut
.
bGPLogicIn1
bGPLogicIn2
bGPLogicIn3
BOOL
Binary logic
: Input signals
• The logic operation is selected in
C00820
.
• The result is output at output
bGPLogicOut
.
nGPCompareIn1_a
nGPCompareIn2_a
INT
Analog comparison
: Input signals
• The comparison operation is selected in
C00680
.
• Hysteresis and window size can be set in
C00680
and
C00682
.
• If the comparison statement is true, the output
bGPCompareOut
will be set to
TRUE.
bGPDFlipFlop_InD
bGPDFlipFlop_InClk
bGPDFlipFlop_InClr
BOOL
D-FlipFlop
: Input signals
• Data, clock and reset input
Free inputs
The following inputs can freely be interconnected on the application level.
The signals can be transferred from the I/O level to the application level via these inputs.
bFreeIn1 ... bFreeIn8
BOOL
Free inputs for digital signals
wFreeIn1 ... wFreeIn4
WORD
Free inputs for 16-bit signals
dnFreeIn1_p ... dnFreeIn2_p
DINT
Free inputs for 32-bit signals
Identifier
Data type
Value/meaning
wDriveControlStatus
WORD
Status word of the controller (based on DSP-402)
• The status word contains information on the currents status of the drive
controller.
• See the "
wDeviceStatusWord status word
" subchapter of the chapter on device
control for a detailed description of the bit assignment.
wStateDetermFailNoLow
WORD
Display of the status determining error (LOW word)
Identifier
Data type
Information/possible settings