8400 StateLine C | Reference manual
Parameter reference
Parameter list | C00800
646
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
C00800
C00801
C00802
C00803
C00804
Parameter | Name:
C00800 | L_MPot_1: Upper limit
Data type: INTEGER_16
Index: 23775
d
= 5CDF
h
The
L_MPot_1
FB: Upper limit of the motor potentiometer function
Setting range
(min. value | unit | max. value)
Lenze setting
-199.99
%
199.99
100.00 %
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00801 | L_MPot_1: Lower limit
Data type: INTEGER_16
Index: 23774
d
= 5CDE
h
The
L_MPot_1
FB: Lower limit of the motor potentiometer function
Setting range
(min. value | unit | max. value)
Lenze setting
-199.99
%
199.99
-100.00 %
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 100
Parameter | Name:
C00802 | L_MPot_1: Acceleration time
Data type: UNSIGNED_16
Index: 23773
d
= 5CDD
h
The
L_MPot_1
FB: Acceleration time of the motor potentiometer function
Setting range
(min. value | unit | max. value)
Lenze setting
0.1
s
6000.0
10.0 s
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 10
Parameter | Name:
C00803 | L_MPot_1: Deceleration time
Data type: UNSIGNED_16
Index: 23772
d
= 5CDC
h
The
L_MPot_1
FB: Deceleration time of the motor potentiometer function
Setting range
(min. value | unit | max. value)
Lenze setting
0.1
s
6000.0
10.0 s
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 10
Parameter | Name:
C00804 | L_MPot_1: Inactive fct.
Data type: UNSIGNED_8
Index: 23771
d
= 5CDB
h
The
L_MPot_1
FB: Selection of the response if the motor potentiometer is deactivated via input
bInAct
Selection list
(Lenze setting printed in bold)
Info
0 Retain value
Keep output value
1 Deceleration to 0
Deceleration via ramp to 0
2 Deceleration to lower limit
Deceleration via ramp to the lower limit (
C00801
)
3 Without ramp to 0
Step change to 0
4 Without ramp to lower limit
Jump to lower limit (
C00800
)
5 Acceleration to upper limit
Acceleration via ramp to upper limit (
C00800
)
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1