8400 StateLine C | Reference manual
Parameter reference
Parameter list | C00174
564
L
Firmware
≤
11.00 - DMS 8.0 EN - 10/2011
C00174
C00175
C00176
C00177
Parameter | Name:
C00174 | Reduc. brake chopper threshold
Data type: UNSIGNED_8
Index: 24401
d
= 5F51
h
The threshold from which on the brake chopper is controlled is reduced by the voltage value set here.
Setting range
(min. value | unit | max. value)
Lenze setting
0
V
150
0 V
;
Read access
;
Write access
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00175 | Brake energy management
Data type: UNSIGNED_8
Index: 24400
d
= 5F50
h
From version 03.00.00
Selection of the braking procedure
Select response if the brake resistor is controlled
Selection list
(Lenze setting printed in bold)
Info
0 R_Brems
The brake resistor is used. When the threshold voltage
(
C00174
) is exceeded, the brake resistor is energised.
1 RfgStop
The "Ramp function generator stop" signal
(
MCTRL_bRfgStop
) is used. When the threshold voltage is
exceeded (
C00174
), the ramp function generator is
stopped.
2 R HlgStop
The brake resistor and the "Ramp function generator
stop" signal are used. When the threshold voltage is
exceeded (
C00174
), the brake resistor is energised and
the ramp function generator is stopped.
3 FI_ RfgStop
From version 04.00.00
Braking is performed by a superimposed speed setpoint
vibration in conjunction with "Ramp function generator
stop".
4 R FU_ HlgStop
From version 04.00.00
Braking is performed by combining all three braking
procedures.
;
Read access
;
Write access
;
CINH
PLC STOP
No transfer
COM
MOT
Scaling factor: 1
Parameter | Name:
C00176 | Undervoltage threshold for mains OFF
Data type: UNSIGNED_16
Index: 24399
d
= 5F4F
h
This code is for device-internal use only and must not be written to by the user!
Parameter | Name:
C00177 | Switching cycles
Data type: UNSIGNED_32
Index: 24398
d
= 5F4E
h
Counter of different switching cycles and stressful situations
Display range
(min. value | unit | max. value)
0
2147483647
Subcodes
Info
C00177/1
Number of mains switching cycles
C00177/2
Number of switching cycles of the output relay
C00177/3
Short circuit counter
C00177/4
Earth fault counter
C00177/5
"Clamp" counter
;
Read access
Write access
CINH
PLC STOP
;
No transfer
COM
MOT
Scaling factor: 1