Chapter 8: Using the Command Line Interface
484
Specifying the Rack Unit Numbering Mode
This command syntax specifies the numbering mode of rack units on the
asset sensors connected to the PX device. The numbering mode
changes the rack unit numbers.
config:#
assetStrip <n> rackUnitNumberingMode <mode>
Variables:
<n> is the number of the FEATURE port where the selected asset
sensor is physically connected. For the PX device with only one
FEATURE port, the number is always 1.
<mode> is one of the numbering modes:
topDown
or
bottomUp
.
Mode
Description
topDown
The rack units are numbered in the ascending
order from the highest to the lowest rack unit.
bottomUp
The rack units are numbered in the descending
order from the highest to the lowest rack unit.
Specifying the Rack Unit Numbering Offset
This command syntax specifies the starting number of rack units on the
asset sensors connected to the PX device.
config:#
assetStrip <n> rackUnitNumberingOffset <number>
Variables:
<n> is the number of the FEATURE port where the selected asset
sensor is physically connected. For the PX device with only one
FEATURE port, the number is always 1.
<number> is a starting number for numbering rack units on the
connected asset sensor. This value is an integer number.
Summary of Contents for PX3-4000 series
Page 5: ......
Page 627: ...Appendix I RADIUS Configuration Illustration 606 Note If your PX uses PAP then select PAP...
Page 632: ...Appendix I RADIUS Configuration Illustration 611 14 The new attribute is added Click OK...
Page 633: ...Appendix I RADIUS Configuration Illustration 612 15 Click Next to continue...
Page 648: ...Appendix J Integration 627 3 Click OK...
Page 661: ...Appendix J Integration 640 2 Launch dcTrack to import the spreadsheet file...