Bus configuration settings
Manual start is configured, status information after startup:
Value (decimal)
Register
Information
1
Init State
0
0
A running bus can, of course, also be stopped with the standard command and re-configured!
The function AsIOAccWrite() from the library AsIOAcc must now be used to write the respective data to all registers
Vendor1Cfg to Vendor16Cfg and Device1Cfg to Device16Cfg. All vendor and device registers that are not being
used must be set to zero. This does not cause a change in the status registers.
To save the data in remanent memory, the function AsIOAccWrite() from the library AsIOAcc must be used to write
to the two registers in the specified order.
Value (decimal)
Register
Information
2
WRITE rem. memory configuration
1
Command for STACK ON / OPERATIONAL
Status information after error-free configuration:
Value (decimal)
Register
Information
20
"RUN without error if SlaveStatus = 0"
325
"PREOP without errors"
0
No slave errors
The bus can now be started using the standard command for the bus:
Value (decimal)
Register
Information
1
Configuration from rem. memory
3
Command for STACK ON / OPERATIONAL
Status information after error-free startup of the bus:
Value (decimal)
Register
Information
20
"RUN without error if SlaveStatus = 0"
345
"RUN without error if SlaveStatus = 0"
0
No slave errors
4.18.2.8.14 Minimum cycle time
The minimum cycle time defines how far the bus cycle can be reduced without communication errors occurring.
It should be noted that very fast cycles decrease the idle time available for handling monitoring, diagnostics and
acyclic commands.
Minimum cycle time
200 µs