X20 system modules • Motor controllers • X20SM1436
X20 system User's Manual 3.10
2037
4.25.7.15.5.3 Configuration registers with SDC
SDC configuration
Name:
SDCConfig01
This register can be used to enable/disable additional SDC information.
Enabling/disabling the SDC information shows or hides additional cyclic registers. It is comparable to the two
variants of the standard function model with and without SDC information.
Data type
Value
USINT
See bit structure.
Bit structure:
Bit
Description
Value
Information
0
Rising trigger edge
0
Trigger edge
1
Falling trigger edge
1 - 5
Reserved
0
0
Disabled
6
1
Enabled
0
Disabled
7
SDC information
1)
1
Enabled
1)
When the "SDC information" bit is enabled, the "EncOK01" bit is shown in the Automation Studio I/O mapping. This bit is linked to the ModulOK bit and
always indicates its value.
Note:
Neither SDC information nor SDC life sign monitoring is permitted to be changed at runtime.
Module configuration 1 with SDC
The Module configuration 1 register is ignored in the standard function model with SDC information enabled. The
module behaves as if the module configuration were described as follows:
Data type
Value
UINT
See bit structure.
Bit structure:
Bit
Description
Value
Information
0
Meaning of bits 2 and 3 in the register "Input counter value"
1 - 2
Reserved
0
3 - 4
Number of transfer values per X2X cycle
00
1x Δs / Δt (transfer values: Motor settings Motor1Step0)
5 - 6
Resolution of microsteps
11
8-bit microsteps
7 - 15
Reserved
0
Motor settling time
Name:
MotorSettlingTime01
This register determines the motor setting time. The motor settling time determines the minimum time between
when the motor is powered on to when the DrvOk bit is set (see "Error status"). The setting is made in steps of 10 ms.
Data type
Value
Information
USINT
1 to 255
10 ms to 2.55 s, default: 10 ms
Turn-off delay
Name:
DelayedCurrentSwitchOff01
When the SDC life sign monitoring is triggered (i.e. the NetTime timestamp is in the past) the motor is decelerated
at rated current with speed setpoint = 0.
Then the motor is switched off after the delay configured with this register.
Data type
Value
Information
USINT
0 to 255
0 to 25.5 ms in steps of 100 ms (default: 100 ms)