X20 system modules • Analog input modules • X20AI2438
X20 system User's Manual 3.10
203
4.3.7.9.4 Variable assignment in Automation Studio (CANIO)
Read
Write
Name
Data type
Cyclic
Acyclic
Cyclic
Acyclic
Analog signal - Communication channel 01
AnalogStatus01
USINT
●
UnderflowAnalogInput01
BOOL
●
OverflowAnalogInput01
BOOL
●
OpenLineAnalogInput01
BOOL
●
ConversionErrorAnalogInput01
BOOL
●
SumErrorAnalogInput01
BOOL
●
SensorErrorAnalogInput01
BOOL
●
IoSuppErrorAnalogInput01
BOOL
●
AnalogInput01
INT
UINT
●
Analog signal - Communication channel 02
AnalogStatus02
USINT
●
UnderflowAnalogInput02
BOOL
●
OverflowAnalogInput02
BOOL
●
OpenLineAnalogInput02
BOOL
●
ConversionErrorAnalogInput02
BOOL
●
SumErrorAnalogInput02
BOOL
●
SensorErrorAnalogInput02
BOOL
●
IoSuppErrorAnalogInput02
BOOL
●
AnalogInput02
INT
UINT
●
HART - Communication channel 01
PvInput01_01
REAL
(UDINT)
1)
●
PvInput01_[02…15]
REAL
●
PvUnit01_[01…15]
USINT
●
HART - Communication channel 02
PvInput02_01
REAL
(UDINT)
1)
●
PvInput02_[02…15]
REAL
●
PvUnit02_[01…15]
USINT
●
HART - Extension register channel 01
PvCountHartRequest01
UINT
●
PvCountHartTimeout01
UINT
●
PvCountHartRxError01
UINT
●
PvCountHartFrameError01
UINT
●
PvNodeFound01
UINT
●
PvNodeError01
UINT
●
HART - Extension register channel 02
PvCountHartRequest02
UINT
●
PvCountHartTimeout02
UINT
●
PvCountHartRxError02
UINT
●
PvCountHartFrameError02
UINT
●
PvNodeFound02
UINT
●
PvNodeError02
UINT
●
1)
REAL data types are not supported by the B&R CANIO Manager on SG3 CPUs. Therefore they can be accessed as UDINT data types in the corresponding
hardware description files.
The UDINT variable data content corresponds to REAL format (IEEE), so it is important to note that using a "Casting" command is not permitted!
Example for C syntax: memcpy(HartREAL_PV,HartUDINT_PV,4)