X20 system modules • Other functions • X20CM4810
X20 system User's Manual 3.10
2159
AnalogInputSamples
Name:
AnalogInputSamples01 to AnalogInputSamples04
If Bit 15 of the corresponding SamplesAnalogInput register is 1, then this register is used cyclically to set the number
of samples for parameter calculation.
Information:
If the register is changed during an active measurement, then the current measurement is discarded
(AnalogInputToggleBit0X is not toggled). Keep an eye out for this, particularly with Enable in contin-
uous mode.
Data type
Value
UINT
See bit structure.
Bit structure:
Data type
Value
Description
> 8191
Invalid
8191 to 1
Characteristic value calculation active for the respective channel in the corresponding analog
input
0
Invalid
The time between 2 samples depends on MaxFrequencyRaw:
Maximum frequency
Sample time
(time between 2 samples)
10000 Hz
38.79 µs
5000 Hz
77.58 µs
2000 Hz
193.94 µs
1000 Hz
387.88 µs
500 Hz
775.76 µs
200 Hz
1939.39 µs
Table 744: Overview of the sample time at the maximum frequency of the raw signal
AnalogInputScale01
This register can be used to specify the scale of the four analog inputs ("AnalogInput01-04"). If the actual value is
greater than the value configured in this register, the respective register for the analog input ("AnalogInput01-04")
is limited to the positive maximum (32767).
For example, if ±128 is configured for AnalogInput04, then the 16 bits represent a value range of ±128 g or without
units if the crest factor has been calculated.
Information:
The configured scaling value is always based on a 100 mV/g sensor. Any sensor that has a different
sensor resolution must be reflected in the configuration.
Bit
Description
15-12
Scaling for AnalogInput04. For possible values, see AnalogInput01.
11-8
Scaling for AnalogInput03. For possible values, see AnalogInput01.
7-4
Scaling for AnalogInput02. For possible values, see AnalogInput01.
3-0
Scaling for AnalogInput01
Value
Description
15 - 9
Invalid
8
±128
7
±64
6
±32
5
±16
4
±8
3
±4
2
±2
1
±1
0
Invalid
Table 745: AnalogInputScale01
AnalogInputScale01Read
This register can be used to read the scale of the analog inputs ("AnalogInput01-04").
Summary of Contents for X20 System
Page 2: ......